Dissolved oxygen refers to the oxygen dissolved in water, measured in µg/L. During operation, if the oxygen content in condensate or feedwater exceeds the value specified in the operating procedures, it is considered dissolved oxygen exceedance. The dissolved oxygen in the condenser and deaerator must be kept within limits; once it exceeds them, adjustment should be made immediately.
| Equipment | Common Cause | Corrective Action |
|---|---|---|
| Condenser | Air in-leakage, low load / low temperature, uneven sealing water | Check vacuum and seals, raise sealing water pressure, adjust makeup water |
| Deaerator | Small atmosphere exhaust opening, low load with low water temperature, leaking drains | Open exhaust valve, raise heating steam, check drains and internals |
| Feedwater pump | Sampling valve admits air after shutdown | Close the sampling valve in time |
Condenser and deaerator dissolved oxygen exceedance can lead to unsafe events, so it must be adjusted immediately once detected. In daily operation, the most frequent causes of deaerator dissolved oxygen exceedance are low water temperature at low load, low ambient temperature, uneven adjustment of condenser sealing water, a small deaerator atmosphere exhaust opening, and air admitted through the feedwater pump sampling valve after shutdown. Correctly identifying the cause allows operators to restore dissolved oxygen to within the qualified range quickly and keep the unit running safely.